How to Troubleshoot & Prevent Open Circuit Faults in Fire Alarm Repeater Panels
By Andrew Erickson
February 11, 2025
Any time you're dealing with fire alarm systems, you're talking about critical life-safety infrastructure. Even the smallest fault can transform a reliable safety net into a dangerous vulnerability. If you've recently seen an open circuit fault message - such as "Supply 1 Open Circuit" - on your repeater panel, you're not alone.
I've worked with numerous fire alarm systems and monitoring setups over the years. One thing I've seen again and again is how a seemingly minor glitch can become a huge headache (or even a safety risk) if it's not resolved at the root cause.
Here, I'll share everything you need to know about open circuit faults in repeater panels and (most importantly) how to fix them for good. Let's jump right in!

What Does "Supply 1 Open Circuit" Mean?
First, a definition: A fire alarm repeater panel is essentially a remote display and control station for your main Fire Alarm Control Panel (FACP). It helps you keep tabs on alarms and events in large facilities, widespread campuses, or multi-building complexes - without having to stand right at the main panel.
When a repeater panel shows a "Supply 1 Open Circuit" fault, it's warning you that its primary power feed has been interrupted. This can happen for a host of reasons:
- Total Loss of Primary Power - Perhaps the building experienced an outage or a disconnected feed.
- Tripped Breaker or Blown Fuse - Power surges or overloads can knock out the supply.
- Loose or Damaged Wiring - Frayed insulation, corroded connectors, or poor installations can disrupt power.
- Failed Power Supply Unit (PSU) - Components age out, or environmental factors (like heat or surges) can damage the PSU.
You never want to ignore a direct power fault - especially not in a life-safety system like a fire alarm panel.
You Have to Locate and Address the Root Cause
In the rush to restore normal operation, it's easy to try obvious fixes: resetting the panel, swapping over to battery backup, or replacing a blown fuse. These patches might get you up and running temporarily, but they won't necessarily address the deeper issue.
Here's why those temporary solutions might fail you in the long run:
- System Reset - Yes, the fault message might clear. But if the issue (say, a failing PSU or a loose wire) is still lurking, that fault can (and likely will) return.
- Relying on Backup Power - Battery backup is important, but it's not a permanent solution. If the main power stays offline for too long, your system will go down when the batteries deplete.
- Overlooking Wiring Issues - A loose wiring connection can disguise itself as "fixed" when it's temporarily stable. However, bumps, temperature changes, or vibrations can make it fail again.
- Replacing Parts Without Root-Cause Analysis - If a fuse keeps blowing, there's a reason - maybe an overloaded circuit or a short. Simply throwing in a new fuse won't solve underlying conditions.
Common Causes of Power Supply Failures in Fire Alarm Systems
Knowing why your panel lost power in the first place helps you prevent future failures. Over the years, I've encountered this list of culprits most often:
- Electrical Surges - Lightning strikes, overloaded circuits, or bad wiring can create voltage spikes. These surges stress or destroy PSU components.
- Aging Infrastructure - Some buildings (especially older ones) have outdated wiring. These vintage wires can degrade to the point of causing repeated electrical problems.
- Environmental Factors - High humidity, excessive dust, or wide temperature swings can corrode connectors and degrade critical components.
- Poor Installation Practices - Loose connections, incorrectly rated fuses, or improper grounding can all cause intermittent or sustained power failures.
- Battery Degradation - When the primary power fails, your backup battery should kick in. But old, undercharged, or poorly maintained batteries may not deliver the power you need.
Address these problems head-on, and you'll avoid a whole world of trouble down the line.

How to Troubleshoot and Resolve Open Circuit Faults
Ready to roll up your sleeves? Here's a systematic approach to diagnosing and fixing "Supply 1 Open Circuit" faults:
- Check the Power Source
- Make sure the building's main power supply is active.
- If there was a recent outage, verify that power is fully restored and stable.
- Inspect the Electrical Circuit
- Locate the breaker or fuse feeding the repeater panel.
- If a breaker is tripped, reset it. Does it trip again immediately? That's a sign of a deeper electrical fault.
- If a fuse is blown, replace it with the correct rating. Again, repeated failures signal something bigger.
- Examine the Wiring
- Open the panel and check for loose or damaged wires, frayed insulation, or corrosion.
- Double-check connections against the fire alarm documentation.
- If anything's out of order, correct it or call in a qualified technician.
- Test the Power Supply Unit (PSU)
- Use a multimeter to check the PSU's output voltage.
- Compare your readings to the manufacturer's specs.
- If the PSU's output is weak or non-existent, it might be time for a replacement.
- Verify Backup Power
- Inspect your battery's voltage and charge level.
- Clean and tighten battery terminals.
- If the battery is "past its prime", swap it for a new one to keep your system protected during outages.
Once you've completed each of these steps, power your system back up. If all is well, you should see that pesky open circuit fault message disappear for good.
Redundant Power Supplies Prevent System Outages
When you're dealing with mission-critical systems, it's always smart to have a Plan B (and sometimes a Plan C). Redundant power supplies are designed so that one failure can't take down the entire network. Many fire alarm systems incorporate:
- Primary Power (AC Mains): The main source, connected to your building's electrical grid.
- Backup Battery: Typically provides 24 to 72 hours of power, depending on system size and regulations.
- Secondary Sources: Some facilities add a second AC circuit or a generator to increase reliability.
A strong monitoring system can keep an eye on these multiple power feeds at once, so you'll know right away if any part of your redundancy chain has failed.
How to Prevent Future Open Circuit Faults
Prevention beats treatment any day, especially when we talk about emergencies. After spending time (and money) on a fix, you definitely don't want that same issue showing up again. Here's how you can guard against future power-supply headaches:
- Regular Power Checks: A quick monthly test of both AC and battery power can highlight problems early.
- Install Surge Protection: Guard your panel against voltage spikes with surge protectors or UPS (Uninterruptible Power Supply) systems.
- Stay Current on Firmware: If your system relies on software-based monitoring or control, keep it updated to avoid weird glitches.
- Routine Wire Inspections: Tighten connections, remove corrosion, and look for any damage.
- Control Room Environment: Keep your panels in a clean, dry, temperature-controlled space as much as possible.
Fire Alarm Monitoring Is Essential for Compliance
Now for the bigger-picture angle: for most industries, you have to maintain a properly functioning fire alarm system - it's not optional. Regulatory bodies like NFPA and OSHA require that your fire alarms work 24/7. A persistent power fault isn't just a threat to safety. A persistent power fault can also:
- Fail Fire Safety Inspections - Local authorities often check alarm systems for operational readiness.
- Increase Liability - In case of an emergency, a faulty alarm can expose you to major legal risks.
- Bring Fines & Penalties - Repeated non-compliance can translate to hefty fines.
An advanced monitoring system can help you stay compliant by logging faults, sending real-time alerts, and keeping your alarm performance within code requirements.
A Smarter Approach to Fire Alarm Monitoring
Even with diligent maintenance, issues can happen. That's why I always recommend a proactive monitoring solution. By detecting failures the moment they occur, you can respond before any real damage has been done.
Digitize builds systems like this that minimize downtime, speed up troubleshooting, and keep your fire alarms (and repeater panels) online. The System 3505 Prism LX monitoring system gives you:
- Real-Time Monitoring: Catch power failures or wiring faults instantly. This way, you can step in before they worsen.
- Remote Alarm Notifications: Get texts or emails (or forward alarms to a central monitoring station) no matter where you are.
- Comprehensive Diagnostics: Quickly pinpoint root causes using detailed system reports.
- Easy Integration: The Prism LX plays nicely with both standalone repeaters and full-scale FACP networks.
Throwing the Prism LX into the mix means your entire fire alarm ecosystem remains transparent, easier to manage, and far more resilient.
Fire Alarm Repeaters Improve Large-Scale Facility Safety
If you're running operations in a major campus, industrial complex, or hospital, you can't just rely on a single control panel in a locked room somewhere. Repeater panels are significant because they:
- Speed Up Response - Security teams or facility managers can see alarms from multiple vantage points.
- Provide Coverage - Large buildings often require multiple panels for adequate visibility.
- Add Redundancy - If one panel goes down, a repeater can still display critical alarms so you're never left in the dark.
Given how important repeaters are, making sure they have stable power isn't just a nice idea - it's downright essential.
The Connection Between Fire Alarm Monitoring and Building Management Systems (BMS)
You might also have a Building Management System (BMS) in play to automate responses. These responses can include unlocking emergency exits, shutting down HVAC to prevent smoke spread, or activating emergency lighting. When you integrate your fire alarm monitoring with a BMS, you get:
- Automated Emergency Actions: Trigger protocols instantly when an alarm is detected.
- Energy Efficiency: A BMS can identify power usage anomalies. This helps you spot issues before a fuse blows.
- Real-Time Fault Detection: An open circuit event can be logged and displayed for immediate action.
Keep Your Fire Alarm System Powered and Protected
Seeing a "Supply 1 Open Circuit" fault - or other open circuit fault message - on your fire alarm repeater panel isn't just a blinking nuisance. It's an urgent signal about a potentially serious power problem. You want to investigate, fix, and prevent a recurrence ASAP.
Don't wait until a real emergency draws attention to the flaws in your fire alarm system. Whether you need help with an open fault or you're interested in quality fire alarm monitoring, Digitize has you covered.
- Call us at 973-663-1011
- Email us at info@digitize-inc.com
Let's work together to keep your facility safe, compliant, and fully protected around the clock!

Andrew Erickson
Andrew Erickson is an Application Engineer at DPS Telecom, a manufacturer of semi-custom remote alarm monitoring systems based in Fresno, California. Andrew brings more than 18 years of experience building site monitoring solutions, developing intuitive user interfaces and documentation, and...Read More