DGM-32M
Product Information
DGM-32M PANEL
The DGM-32M Series includes data gathering modules that monitor dry contacts. The unit communicates with the System 3505 Prism LX™ head-end via a dedicated cable pair. The System 3505 Prism LX™ polls all DGM panels for any change in status, which are then passed to the head-end. All status changes are held in memory by the DGM, even if the condition clears. Inputs are supervised so that any break in the input circuit will cause a “Trouble” condition to be reported by the zone.
The DGM-32M is suitable for an installation that will begin at 8, 16, or 24 and possibly expand later to 32 End-of-Line resistor alarm inputs without relay control requirements. Order this panel according to how many zones are desired initially: DGM-32-8, DGM 32-16, etc.
All models are housed in steel enclosures housing with a stepdown transformer, tamper switch, CAM lock, data link interface, 60 hour standby battery and built in charger. Each zone can be bypassed using the internal keypad. Out-of-service zones report their condition to the head-end equipment.
All DGM panels are normally powered by 117 VAC through the internal step-down transformer and use a 12 VDC battery as backup (when AC is the main source). Loss of AC power for more than 15 seconds is reported to the System 3505 Prism LX™ for display. The length of time before a loss of power is reported to the system can be set by the user for any value between 1 and 90 seconds. Should the battery voltage drop before a preset level, a “Low Battery” condition will be reported for display. In normal operation, the DGMs internal charger will keep the standby battery at full charge. Should a loss of power occur, all DGM panels are capable of switching from AC to battery power. The DGM-32M switches from AC to battery power without service interruption.
Features
- 8/16/24 zones per panel, EOL (DGM 32- 8, DGM 32-16, DGM 32-24)
- Alarm & trouble indicators per zone via LCD display
- Zone bypass via keypad
- 2 x 16 Character LCD display (illuminated)
- Reports alarm, trouble, secure bypass, low battery, tamper, AC fail and ground fault
- AC or DC power, tamper switch
- Form C relay can be turned On, Off, or Momentary with relay control option on the System 3505 Prism LX™
- Built-in lightning protection on all zone inputs
- In circuit programmable
- Barrier Strips “pop out” for easy service
- Setup mode down loadable from System 3505 Prism LX™
- Built-in battery charger & watchdog timer
- Compatible with all Digitize DGM models
- Electronics on hinged inner door
- Complies with NFPA 72 standards
- In circuit programmable
Specifications
Enclosure: Steel enclosure with door and cam lock
Dimensions: Height: 15 1/8”, Depth: 4 1/8”, Width: 13 1/2”
Power: 117VAC 50/60 Hertz
Battery: 12VDC Battery backup (12 AH standard)
Input Zones: 8 Zones, end-of-line resistor (4.7K)
Communication Style: RS-422/485 Style 3/6, audio modem, isolated RS 422/485, RS-232, fiber optic, High-level Style 7
Operating Temperature: -40°C to +60°C
Optional Lightning Protection Board: P/N 400471-0002