Mastering Fire Alarm System Programming: Solving Zone Configuration Challenges
By Andrew Erickson
November 20, 2024
Fire alarm systems are your lifelines in an emergency, but programming and troubleshooting them can be a big task. That's especially true when you're integrating with legacy systems or meeting very specific municipal requirements.
A recent conversation between a Digitize client and support engineer John Ermatinger is a good example of these challenges and gives you valuable insights into solving complex zone programming issues.
If you've ever wondered, "Why is my fire alarm system transmitting incorrect codes?" or struggled with cumbersome configurations, I'll walk you through several useful real-world solutions now...
The Problem: Misconfigured Zone Codes and Transmission Errors
Imagine this: your fire alarm system is transmitting incorrect codes to your monitoring center. The discrepancy between programmed codes and transmitted data creates confusion and potential delays in response. In this case, the client faced a similar issue with Zone 10 transmitting improperly.
"What was the box number? Because I was using a different number for my testing," the client asked. John clarified, "5131. I was making 5631."
This "small" issue in code programming was enough to throw the entire zone off-track. Without accurate zone codes, the monitoring system fails to differentiate between alarms, restorations, or troubles. That's a huge problem resulting from a simple typo.
Errors like this show you how precision in programming is essential. You must ensure that every signal is correctly interpreted by monitoring systems and responders.
Use Better Equipment & Get an Expert "Second Set of Eyes"
When dealing with programming errors, relying on massive outdated manuals or guessing and testing isn't ideal. It's better to seek expert help and consider investing in an upgraded system to avoid frustration and wasted time.
"No matter which way I put it in there, I could not get it to come out correctly for the way that you wanted to get the codes to come out."
This demonstrates how misinterpreting zone programming settings can result in repeated failures.
Legacy systems also pose challenges with inflexible programming methods, which is why Digitize equipment has evolved over the years. As John shared:
"Our old DET-6… was an EEPROM-based programmer. If you had to make changes, you had to swap out an EEPROM and get it programmed."
This cumbersome approach not only slows down troubleshooting but also makes even small adjustments labor-intensive.
Modern solutions, by contrast, are designed to eliminate these inefficiencies. Notice how a call to an expert at the manufacturer's HQ revealed all of this useful information.
The Ideal Solution: Modern Tools and Step-by-Step Guidance
Modern systems like the DET-16 Transmitter streamline programming, enabling real-time changes without requiring hardware swaps. But even the best tools require some instruction. John's step-by-step guidance during the call included the following tasks:
Access the Programming Menu:
"Go into the programming function mode by pressing the function key. It'll ask you for the password. Default password is 123456, enter," John advised.
Edit the Zone Settings:
For Zone 10, John instructed, "Enter the box number of 5131. Then for your code, enter 51310." Using the up cursor key, the client navigated to alarm code settings, ensuring proper configurations for alarm and trouble codes.
Set the Rounds:
Municipal requirements often dictate specific "rounds" for alarms and troubles. "They wanted two rounds for their restore," John explained, guiding the client to configure the system accordingly.
Validate Settings and Reset:
After programming, it's crucial to validate the settings and reset the system. "After an upload… it should be manually reset," John emphasized. This ensures that changes take effect without residual errors.
By following these steps, you can avoid common pitfalls and ensure that your fire alarm systems are programmed properly.
Bridging the Gap Between Your Equipment and Municipal AHJ Standards
Your fire alarm systems must adhere to specific standards set by municipalities to ensure consistency across local monitoring systems. These standards often dictate code formats, signal timing, and transmission rounds that you must use.
John elaborated on the importance of timing: "One-third to one-half second timing is fairly typical… If they're station bells, a quarter second will usually ring out okay." Customizing these parameters ensures that signals are neither too fast to be heard/decoded - nor too slow to cause needless delays.
For the client, aligning Zone 10's settings with the city's (AHJ) standards was a critical step. As John pointed out, "Their programming sheet… might tell you exactly what they want." By referring to these documents and adjusting the system accordingly, the client ensured compliance and avoided potential disruptions.
Municipal standards also govern redundancy and fail-safes. For example, the city required specific restore rounds to confirm resolution. "When I sent them a live test, they read to me the four number of rounds… and then the restore went through," the client confirmed, proving that the changes worked.
Coding Accuracy: Alarm and Restore Codes Must Work Together
Alarm codes and restore codes are the "nuts and bolts" of fire alarm monitoring. Alarm codes notify responders of an issue, while restore codes signal when the problem is resolved. Both are required for accurate communication.
"You're transmitting basically a four-digit box code, correct?" John asked during the call. When the client confirmed, John explained how to add specificity: "For your code, you're going to enter 51310." This change ensured that each zone transmitted a unique identifier, enabling dispatchers to pinpoint the location of alarms.
Restore codes play an equally critical role. John explained their configuration: "The alarm restore rounds I have is two, which they wanted two rounds for their restore." These codes ensure that monitoring centers receive timely updates about resolved issues, preventing unnecessary resource deployment. A second "round" of a restore signal protects against an unheard first round.
As the client tested Zone 10, they reported, "The restore went through, and they said, yep, everything's restored. That was all strong and correct."
Testing and Troubleshooting are Your Keys to Long-Term Reliability
Programming fire alarm systems isn't just about inputting codes. You must verify that they work as intended. This is where thorough testing and troubleshooting come into play.
Live testing simulates real-world conditions, allowing technicians to validate settings. John guided the client through this process: "I'm going to short Zone 10… Okay, so now that's finally saying 51310, and then it says Zone 10 alarm on my end." This confirmation ensured that the system was transmitting correctly.
Incorporating regular testing into maintenance routines ensures long-term reliability. By simulating alarms, troubles, and restores under various conditions, you can proactively identify and resolve issues.
Fine-Tuning for Timing and Signal Integrity
The speed and accuracy of signal transmission are paramount in fire alarm systems. Improper timing can lead to decoding errors or delays, impacting response times.
Remember how John highlighted this balance earlier: "If they're station bells, a quarter second will usually ring out okay. But somebody might say, you know, that's a little fast." Fine-tuning these settings to match municipal requirements ensures optimal performance.
Signal integrity is also critical when integrating modern systems with legacy components. "That was probably one of the nicest things we did when we came out with the DET-16… through the software upload," John explained. This functionality allowed for more frequent adjustments by Digitize clients, reducing errors caused by timing mismatches or outdated hardware.
Find a Fire Alarm Vendor Who Will Support You Like This
A major takeaway from the call was the importance of collaboration. John's expertise, combined with the client's proactive approach, resulted in a successful resolution. At the end of the call, the client said, "I think we got it… I think I'm going to call them and send a test on that Zone 10."
John also highlighted Digitize's commitment to ongoing support: "If you need anything else, you got the number. Give me a holler."
Call Transcript (Excerpts from this Tech Support Call)
Here's are some selected snippets from this support call between John and a Digitize client. Ask yourself whether you're getting support like this from your current vendors:
Digitize Client: What was the box number? Because I was using a different number for my testing.
Engineer John: 5131. I was making 5631.
Digitize Client: Okay, 5131. Let me just get a note. Got it. So, yeah, the rest of the box can remain the same without changing it. We're just changing Zone 10.
Engineer John: Correct. You're transmitting basically a four-digit box code, correct?
Digitize Client: Yes, a four-digit box code. That's what they're getting, and then they want each zone after that. For instance, if we were doing Zone 12, it would just be box 5131 and then Zone 12. When you do Zone 1, you're getting 5131 transmitted, correct?
Engineer John: Correct. And the last one, are they going to want 5130 or 51310?
Digitize Client: 51310. They want it to be Zone 10.
Engineer John: All right, so in the programming function mode, press the function key. It'll ask you for the password. Default password is 123456. Enter. Then clear twice. It should say "DET-16 Transmitter Version 108."
Digitize Client: Got it.
Engineer John: Hit function twice. Select Zone 10. Enter the box number 51310. Then use the up cursor to navigate to the alarm code. Enter zero. The alarm restore rounds should be set to two. Does that align with what they need?
Digitize Client: Yes. I think that's what they wanted. All right, let me do that.
...
Engineer John: If you're running into timeouts, you can either wait for it to reset, or manually reset the board.
Digitize Client: Okay. I've reset it. Now I'm back to the main menu. It's a bit cumbersome, but I think I've got it.
Engineer John: It's designed that way to avoid accidental changes. Once you're back in, re-enter the password and repeat the steps for programming Zone 10. After changes, always manually reset the system to ensure the settings take effect.
Digitize Client: I'm back in. All right, box number is 51310, alarm code is zero, alarm restore rounds are two. Moving to the trouble code. I'll set that as zero, with three trouble rounds. Trouble restore rounds, I'll set to one. Does that look correct?
Engineer John: That's perfect. Make sure you save and reset to confirm the configuration.
...
Digitize Client: They were reading back the tests. I sent them Zone 10, and they said, "We're getting a restore now." It was all correct. Looks like it's working.
Engineer John: Great. Did you check with them about timing? Quarter-second intervals are typical, but if it's not flagged, you're likely fine.
Digitize Client: No complaints so far. They've been reading the codes back correctly.
Engineer John: If there's an issue with timing, you can adjust the transmission speed in the general settings. Most municipalities are fine with quarter-second or half-second intervals.
...
Digitize Client: I've been testing Zone 10 live. Now it says "Zone 10 alarm" on my end, and I heard it transmit as 51310.
Engineer John: That's exactly what we were aiming for. Listening for that final digit ensures it's transmitting the correct box number and zone.
...
Digitize Client: Just to clarify, what's your recommendation for setting the restore and trouble codes for the rest of the zones?
Engineer John: Use the same structure: alarm rounds set to two, trouble rounds set to three, and restore rounds to one. Keep the default for non-essential settings like battery trouble unless you're explicitly told otherwise.
Digitize Client: Makes sense. I'll replicate that for all the zones.
...
Digitize Client: This DET-16 Transmitter is a huge improvement. With the DET-6, we had to swap out EEPROMs just to make changes. Now, uploading through the software is so much faster.
Engineer John: That's one of the best features of the DET-16. It simplifies adjustments and reduces downtime during reconfigurations.
...
Digitize Client: I think we've got everything resolved. I'll call in another test to confirm Zone 10 is stable.
Engineer John: Perfect. If you need anything else, you've got my number. Don't hesitate to reach out.
Digitize Client: Thanks so much. You've been a great help.
Conclusion: Making Programming Easier for Everyone
Programming fire alarm systems doesn't have to be a massive undertaking. With modern tools like the DET-16 Transmitter and expert guidance from professionals like John Ermatinger, you can manage even very complex configurations.
If you're struggling with zone programming or having trouble aligning your system with municipal requirements, you can get help.
Call Digitize for one-on-one support (even if you're not a client yet) and equipment options tailored to your needs. Call 1-800-523-7232 or email info@digitize-inc.com now to speak with John and his team of engineers.
Andrew Erickson
Andrew Erickson is an Application Engineer at DPS Telecom, a manufacturer of semi-custom remote alarm monitoring systems based in Fresno, California. Andrew brings more than 17 years of experience building site monitoring solutions, developing intuitive user interfaces and documentation, and...Read More